Engineering and remote access
7.5 SIMATIC STEP 7
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
217
●
Time A: Wait time until the short-time interruption
The parameter is used to define the time that must elapse after the "Buffer mode" alarm
message, before the output voltage at output 1 is automatically interrupted when the
power supply returns during buffering.
Select this time so that it is significantly longer than the expected time for safely and
reliably running down the PC. This is because at the latest when this time expires, the
voltage at output 1 is automatically interrupted - independent of whether the shutdown
has been completed or not.
●
Time B: Duration of short-time interruption
The parameter is used to define the time for which output 1 is interrupted during buffering
when the power returns (for example to restart a PC after it has been run down).
●
Time C: Waiting time after shutdown completed
The parameter is used to define the time that must additionally elapse after the shutdown
has been completed (i.e. after the client can no longer be accessed via a network ping),
before the output voltage at output 1 is interrupted when the power supply returns during
buffering.
●
Define that only output 1 is activated when starting from a battery module
If the SITOP PSU8600 is activated with the energy from a battery module, then only
output 1 is activated. The other outputs are only activated once the supply voltage is
connected/is available.
Output parameters
Outputs are parameterized at the basic units and at the expansion modules in the same
identical way. You can find a list of the parameters in Chapter "Parameterizing output 1
(Page 219)".
PROFIenergy parameters
Parameter
Value range
Default setting
Enable PROFIenergy on this device
Yes/no
No
Time to pause
0 - 2147483647
0 ms
Time to operate
0 - 2147483647
0 ms
Minimum pause time
0 - 2147483647
0 ms
Maximum pause time
0 - 2147483647
0 ms
Power consumption in saving mode
0.000 - 100000.000
0.00 kW
Power consumption during operation
0.000 - 100000.000
0.00 kW
Energy consumption to pause
0.000 - 100000.000
0.00 kWh
Energy consumption to operation
0.000 - 100000.000
0.00 kWh