Technical data
9.2 Output data
Power supply system SITOP PSU8600
386
Manual, 09.2018, A5E36758446-5-76
Basic unit
6EP3436-8SB00-2AY0
Basic unit
6EP3437-8SB00-2AY0
•
Comment
no derating in conjunction with the expansion module SITOP CNX8600 and total
load of the outputs at the basic unit max. 240 W or 480 W
See "Figure 9-7 Output power as a function of the ambient temperature for
SITOP PSU8600 6EP3436-8SB00-2AY0 (Page 391)" and "Figure 9-8 Output
power as a function of the ambient temperature for SITOP PSU8600 6EP3437-
8SB00-2AY0 (Page 391)".
Output current per output
20 A
40 A
Output active power (typical)
480 W
960 W
Overload capability
Complete system can be overloaded
up to 150 % for 5 s/min
Complete system can be overloaded
up to 150 % for 5 s/min
Can be connected in parallel to in-
crease the power rating
Yes, inclined output characteristic can
be selected using a DIP switch
Yes, inclined output characteristic can
be selected using a DIP switch
Number of devices that can be con-
nected in parallel to increase the power
rating
2
2
1)
Can be expanded using a maximum of 4 expansion modules