Operator control at the device
3.3 Overload shutdown and carrying out a reset
Power supply system SITOP PSU8600
86
Manual, 09.2018, A5E36758446-5-76
Carrying out a reset with the button at the device
The output can be reset using the button. This resets the electronic shutdown of the output,
caused by an overload condition.
①
Button (illuminated with an LED)
The initial situation is an electronic shutdown as a result of an overload condition. This is
signaled using LED "ON/OFF/RST" in button
①
:
LED in the button
Meaning/handling
Lit red
Electric shutdown due to an overload.
Wait time until a reset is possible: 5 seconds.
Flashes red
Output ready for a reset
Press the button to switch-on the output again.
Lit green
The reset was carried out, the output was switched-on again.
Procedure
1.
After an electronic shutdown, wait 5 seconds (LED "ON/OFF/RST" of the output is lit red).
2.
Press the button of the output, which is ready for a reset (LED "ON/OFF/RST" of the
output flashes red).
Electronic shutdown is reset, and the output has been switched-on again (LED
"ON/OFF/RST" of the output is lit green).
Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically switched off according to the shutdown characteristics.
To prevent a new shutdown, before carrying out a RESET, remove the cause of the
overload.