Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
380
Manual, 09.2018, A5E36758446-5-76
ID
Severity
Event
Help text
74
N
Battery capacity tracing test can-
celed. Battery not fully charged
The battery capacity tracing test can not be started because
of not fully charged batteries.
75
N
Battery capacity tracing test can-
celed. Insufficient system load
The battery capacity tracing test is canceled because of
insufficient system load.
76
N
Battery capacity tracing test can-
celed by user
The battery capacity tracing test is canceled by the user.
77
N
Battery capacity tracing test can-
celed. Buffering started
The battery capacity tracing test is canceled because of
started buffering mode.
78
N
Battery capacity tracing test can-
celed. Input voltage too high
The battery capacity tracing test is canceled because of too
high input voltage.
Alarm list SITOP BAT8600
The IDs for the BAT8600 module alarms depend on the number of the particular battery
module:
●
Battery 1: 100 + ID
●
Battery 2: 130 + ID
●
Battery 3: 160 + ID
●
Battery 4: 190 + ID
●
Battery 5: 220 + ID
ID
Severity
Event
Help text
1
MD
Incompatible battery detected
The battery is a type that is not compatible with the configu-
ration. The battery cannot be commissioned.
2
MR
New battery detected
New battery detected
3
MR
Unknown battery
Data cannot be read correctly from the battery. Battery is
defective or not supported by SIEMENS.
4
MD
Module with reduced power de-
tected.
A module with reduced power was detected. Deviating sys-
tem behavior may be possible.
5
MR
Module with excessive power de-
tected.
A module with excessive power was detected. Normal oper-
ation of the system is possible.
6
MR
Unexpected module type detected. Unexpected module type detected.
7
N
Different serial number detected
Different serial number detected
8
N
Different firmware version detected Different firmware version detected
10
MR
Deep discharge battery
Battery is deep discharged - no buffering possible.
11
MD
Battery defective
Battery defective - neither buffer nor charging operation is
possible
12
MD
Fuse is defective (battery index:
{1:d})
Fuse is defective.
13
MD
Battery temperature high, battery
switched off
The temperature of the battery is too high. The battery was
switched off for safety reasons. Buffering is no longer possi-
ble depending on the number of connected batteries!
14
MR
Warning before battery over-
temperature
Battery temperature too high – battery service life is short-
ened