
Engineering and remote access
7.4 SIMATIC STEP 7 in the TIA Portal
Power supply system SITOP PSU8600
180
Manual, 09.2018, A5E36758446-5-76
Assigning a battery module to the UPS module
In order that the UPS module can buffer, you must assign at least one battery module to the
UPS module.
Procedure
1.
Select the SITOP PSU8600 in the Device view.
2.
Navigate in the Hardware catalog to the UPS modules under "Power supply and
distribution\Power supplies\SITOP PSU\UPS8600/Battery".
3.
Select the required battery module in the Hardware catalog.
4.
Drag the battery module and drop it into the Device view.
Alternatively, the battery module can be added by double-clicking on the entry in the
hardware catalog.
5.
Drag and drop the battery module to the required slot below the SITOP PSU8600.
The battery module is inserted in the selected slot.
6.
Save the hardware configuration.
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...