Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
342
Manual, 09.2018, A5E36758446-5-76
SubDevices
The parameters for the battery modules are listed under the "SubDevices" nodes.
SITOP BAT8600 battery modules
ActualState
Display name
Data type
Definition
Description
ModuleOperatingState
Enumeration
MultiStateDiscrete-
Type
Battery status
ModuleStateOfHealth
Integer
AnalogItemType
State of health of the battery mo-
dule
ModuleCapacity
Integer
AnalogItemType
Capacity of the battery module
ModuleTemperature
Integer
AnalogItemType
Battery temperature
ModuleOperatingHours
Integer
AnalogItemType
Total operating time of the batteries
ModuleStateLed
Object
Sitop_8600_LedType Actual state of the LED display
"O.K."
Alarm
Display name
Data type
Definition
Description
Alarm_MR_BatteryCommunication
Disconnected
Boolean
PropertyType
Communication to the battery is
interrupted. Buffering is still possi-
ble, the battery charge level has
been reduced to a minimum how-
ever.
Alarm_MD_BatteryDefect
Boolean
PropertyType
Battery defective - neither buffer
nor charging operation is possible
Alarm_MD_BatteryParameters
Corrupt
Boolean
PropertyType
The battery configuration is corrupt.
Battery behavior may deviate.
Alarm_MD_BatteryTemperature
HighError
Boolean
PropertyType
Battery temperature is too high and
the battery was shut down for safe-
ty reasons. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MD_BatteryTemperature
LowError
Boolean
PropertyType
The battery temperature is too low.
The battery will not operate in this
situation. Buffering is no longer
possible depending on the number
of connected batteries.
Alarm_MD_IncompatibleBatteryDe-
tected
Boolean
PropertyType
The battery is a type that is not
compatible with the configuration.
The battery cannot be commis-
sioned.
Alarm_MD_LessCapableBattery
Detected
Boolean
PropertyType
A module with reduced power was
detected. Deviating system beha-
vior may be possible.
Alarm_MR_BatteryDeepDischarge Boolean
PropertyType
Battery is deep discharged - no
buffering possible.
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...