Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
301
Configuring UPS8600
Parameters of the UPS module
●
Maximum charging power
Select between "High" and "Low".
The charging power can be reduced from the preset 120 W to 60 W to reduce the effect
of the charging power on the power that is available at the outputs. In this way, the UPS
module can be adapted to power supply systems with a total output power of 480 W.
●
Battery test interval
Select at which time intervals the battery test should be performed.
●
Buffer timer enabled
Shows whether the buffer timer is activated
●
Maximum buffer time
Maximum buffering time.
Configuring BAT8600
Battery modules do not have to be configured.