Data
Description
Data type
4 = ReadyForRestart
Output ready for reset:
5 = ErrorOff
Output switched off (error)
6 = Boot
Output switched off (startup)
7 = Running
Output switched on (nor-
mal operation)
8 = Overload
Output in overload mode:
9 = Limit
Output current limited to
response threshold:
10 = Overloaded
(SystemOverload)
Output in overload mode
(with derating):
11 = LimitAfter
(SystemOverload)
Output current limited
(with derating)
12 = Locked
Output switched off as the
UPS8600 is being charged
Fill byte(s)
-
Unsigned8
LED color
Actual LED color. Each
LED is represented by 2
bits:
•
Bit0/1: OK
•
Bit2/3: Man/Remote
•
Bit4/5: Output
•
Bit6-15: Not used
0
LED is off
Unsigned16
1
LED lit green
2
LED lit red
3
LED lit yellow
LED state
Actual display status of
the LEDs. Each LED is
represented by 2 bits:
•
Bit0/1: OK
•
Bit2/3: Man/Remote
•
Bit4/5: Output
•
Bit6-15: Not used
0
LED is off
Unsigned16
1
LED is lit
2
LED flashes at 1 Hz
3
LED flashes at 2 Hz
Index 33: Buffer state information (reading)
Data
Description
Data type
Buffer component disabled via control contact or
control command (0/255)
The buffer function is either disabled via one or
more control contacts of the buffer modules or via
a control command.
Unsigned8
Buffer ready (0/255)
Buffer component ready for buffering.
Unsigned8
System charging state (0-120 %)
System charge status
Unsigned8
Buffer component disabled via control contact
(0/255)
Buffer component disabled via control contact:
Unsigned8
Actual total UPS charging power [10mW]
Actual charging energy, total
Unsigned16
System started from battery (0/255)
The system is started with the energy provided by
a battery module.
Unsigned8