Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
405
Safety, approvals, EMC
10
10.1
Safety
Basic units
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
Expansion modules
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
6EP4436-8XB00-0DY0
Primary/secondary galvanic
isolation
Yes
1)
-
Electrical isolation
SELV output voltage Uout according to EN 60950-1 and EN 50178
Protection class (EN 61140) Class I
Class III
Degree of protection
(EN 60529)
IP 20
IP 20
Leakage current, max.
3.5 mA
-
Test voltage
See Section "Test voltages (Page 406)".
1)
The transformer inside the device complies with IEC 61558-2-16
Buffer modules
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
UPS module
6EP4197-8AB00-0XY0
Electrical isolation
-
SELV output voltage Uout according to
EN 60950-1 and EN 50178
Protection class (EN 61140) Class III
Class III
Degree of protection
(EN 60529)
IP 20
IP 20
See also
Test voltages (Page 406)
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...