Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
262
Manual, 09.2018, A5E36758446-5-76
SITOP BUF8600 4 s/40 A and SITOP BUF8600 10 s/40 A
Data
Description
Data type
Internal powerbus
voltage [10mV]
Internal supply voltage
Unsigned16
Internal buffer voltage
[10mV]
Internal buffer voltage
Unsigned16
Charging current
[10mA]
Charge current
not supported (always 0)
Unsigned16
Load current [10mA]
Load current
not supported (always 0)
Unsigned16
Module operation state Operating state
0 = Off
Buffer component is in the
"Off" operating state.
Unsigned8
1 = Boot
Buffer component is po-
wering up.
2 = Default
Complete buffer readi-
ness: The energy storage
device of the buffer com-
ponent is fully charged
(normal operation).
3 = Buffering
The buffer component is
operating in the buffer
mode: The power supply
system is supplied via the
buffer component(s).
4 = ErrorOff
Shutdown after error: A
fault/error has occurred
when operating the buffer
component. The buffer
component is not opera-
tional and must be re-
started by switching off
the supply voltage and
switching it on again.
5 = ReadyForRestart
Buffer component is
ready to be switched on
again
6 = NotFully
ChargedReady
Ready for buffering as the
energy storage device of
the buffer module has
been sufficiently charged.
7 = NotFully
ChargedNotReady
Not ready for buffering as
the energy storage device
of the buffer module has
not been sufficiently
charged and is presently
being charged.
8 = Disable
Buffer component dis-
abled.