Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
368
Manual, 09.2018, A5E36758446-5-76
Alarm list SITOP CNX8600
6EP4436-8XB00-0CY0 (4x5 A) and 6EP4437-8XB00-0CY0 (4x10 A)
ID
Severity
Event
Help text
0
F
Incorrect checksum.
Defective firmware detected. Device must be reactivated
with a new firmware update.
1
F
Output switched off due to over-
heating.
Overheating was detected at the output. The output has
been switched off.
2
MD
Advance warning against overheat-
ing at output.
Risk of overheating detected at the output. Immediate load
reduction is recommended.
3
F
Output switched off due to over-
heating.
Overheating was detected at the output. The output has
been switched off.
4
MD
Advance warning against overheat-
ing at output.
Risk of overheating detected at the output. Immediate load
reduction is recommended.
5
F
Output switched off due to over-
heating.
Overheating was detected at the output. The output has
been switched off.
6
MD
Advance warning against overheat-
ing at output.
Risk of overheating detected at the output. Immediate load
reduction is recommended.
7
F
Output switched off due to over-
heating.
Overheating was detected at the output. The output has
been switched off.
8
MD
Advance warning against overheat-
ing at output.
Risk of overheating detected at the output. Immediate load
reduction is recommended.
9
MR
Overload shutdown of the output.
Invalid overload occurred at the output. The output was
switched off.
10
N
Overload detected at the output.
Output current at the output is above the preset response
threshold but is still within the permissible overload profile.
The output current is about to be limited.
11
N
The actual value of the output
current is above the set advance
warning threshold.
The actual value of the output current is above the config-
ured advance warning threshold and is below the response
threshold.
12
MR
Overload shutdown of the output.
Invalid overload occurred at the output. The output was
switched off.
13
N
Overload detected at the output.
Output current at the output is above the preset response
threshold but is still within the permissible overload profile.
The output current is about to be limited.
14
N
The actual value of the output
current is above the set advance
warning threshold.
The actual value of the output current is above the config-
ured advance warning threshold and is below the response
threshold.
15
MR
Overload shutdown of the output.
Invalid overload occurred at the output. The output was
switched off.
16
N
Overload detected at the output.
Output current at the output is above the preset response
threshold but is still within the permissible overload profile.
The output current is about to be limited.
17
N
The actual value of the output
current is above the set advance
warning threshold.
The actual value of the output current is above the config-
ured advance warning threshold and is below the response
threshold.
18
MR
Overload shutdown of the output.
Invalid overload occurred at the output. The output was
switched off.
Содержание SITOP PSU8600