Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
365
ID
Severity
Event
Help text
15
MD
Overload detected at the output.
Output current at the output is above the preset response
threshold but is still within the permissible overload profile.
The output current is about to be limited.
16
MR
The actual value of the output
current is above the set advance
warning threshold.
The actual value of the output current is above the config-
ured advance warning threshold and is below the
response threshold.
17
F
Faulty communication to the mo-
dule.
Communication with the expansion module is faulty. All
outputs on the expansion module have been switched off.
18
F
Internal communication error
A communication problem exists between primary and sec-
ondary side controllers. All outputs of the power supply
system have been switched off.
19
F
Internal communication error
A communication problem exists between the PROFINET
module and the main controller.
20
F
Critical error.
A critical error occurred. All outputs of the power supply
(module/system) have been switched off.
21
MD
Critical error.
General critical error occurred. The device may therefore
behave inconsistently.
22
MR
General error.
General error occurred. Device behavior remains consistent,
however.
23
MR
System is ready to switch on again. System can be switched on again after automatic shutdown
due to impermissible operating condition. Reset by switch-
ing the supply voltage off and on.
24
MR
System is ready to switch on again. System can be switched on again after automatic shutdown
due to impermissible operating condition. Reset by switch-
ing the supply voltage off and on.
25
MR
Buffer mode
The power supply system is supplied via the buffer expan-
sion module(s).
26
N
Device starting up.
Device starting up.
27
N
Device is in manual mode.
The device was switched to manual mode. Remote configu-
ration and control are not possible.
28
MR
Output is ready to be switched on. Output is ready to be switched on again after automatic
overload shutdown.
29
MR
Current limit on the output after
occurrence of an overload.
Output is in overload mode. The output current is limited to
the configured response threshold.
30
N
Output was switched off manually. Output was switched off manually directly on the device.
31
MR
Output switched off during buffer-
ing
Output switched off during buffering
32
N
Output was switched off.
Output was switched off.
33
N
Output was switched on.
Output was switched on.
34
F
Safety shutdown of the output.
A critical error occurred. This output was shut down by the
power supply system.
35
F
Expansion module is not available. Expansion module was not found. Power supply system
response deviates from the configuration.
36
F
Invalid number of modules.
Invalid number of modules detected. Invalid slot.
37
MR
New unconfigured module detect-
ed.
New unconfigured module detected.
38
F
Performing firmware update.
Performing firmware update. Read/write access is currently
not possible.