![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918079.webp)
2 - 19
2 Design
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
2-3
W
irin
g
2
2-
3-4 Wiring for
Main C
irc
uit T
erminals
For inverter wiring, crimp terminal, and terminal screw tightening torque, refer to the table below.
• Each table shows an example of connecting the standard 3-phase motor with four poles to an
inverter.
• For the molded case circuit breaker (MCCB), select an appropriate product in consideration of the
breaking capacity.
• For compliance with the UL standard requirements, be sure to perform wiring according to
A-4
UL/cUL Standards Cautions
on page A-10, which includes the use of UL-compliant Class-J fuses.
• Tighten the terminal block screws with the specified torque. Weak tightening may result in a short-cir-
cuiting accident or fire. Conversely, overtightening these screws may cause damage to the terminal
block or the inverter.
z
3-phase 200-V Class
*1. The wire size is based on H-IV wire (with a heat resistance of 75°C).
*2. For compliance with the UL standard requirements, be sure to perform wiring according to
A-4 UL/cUL Stan-
dards Cautions
on page A-10.
Recommended Cable Size, Wiring Device, and Crimp Terminal
Model
Heavy/
Light load
mode
Maximum
applicable
motor
capacity
[kW]
Rated
input
current
[A]
Power cable,
ground cable
[mm
2
]
*1*2
Terminal
screw
size
Tightening
torque
[N
·
m]
*2
Molded
case
circuit
breaker
(MCCB)
*2
3G3MX2-A2001-V1
Heavy load
0.1
1.0
AWG16 (1.25)
M3.5
1.0
5 A
Light load
0.2
1.2
AWG16 (1.25)
5 A
3G3MX2-A2002-V1
Heavy load
0.2
1.6
AWG16 (1.25)
M3.5
1.0
5 A
Light load
0.4
1.9
AWG16 (1.25)
5 A
3G3MX2-A2004-V1
Heavy load
0.4
3.3
AWG16 (1.25)
M3.5
1.0
5 A
Light load
0.75
3.9
AWG16 (1.25)
10 A
3G3MX2-A2007-V1
Heavy load
0.75
6.0
AWG16 (1.25)
M3.5
1.0
10 A
Light load
1.1
7.2
AWG16 (1.25)
10 A
3G3MX2-A2015-V1
Heavy load
1.5
9.0
AWG14 (2.0)
M4
1.4
15 A
Light load
2.2
10.8
AWG14 (2.0)
20 A
3G3MX2-A2022-V1
Heavy load
2.2
12.7
AWG14 (2.0)
M4
1.4
20 A
Light load
3.0
13.9
AWG12 (3.5)
20 A
3G3MX2-A2037-V1
Heavy load
3.7
20.5
AWG12 (3.5)
M4
1.4
30 A
Light load
5.5
23.0
AWG10 (5.5)
50 A
3G3MX2-A2055-V1
Heavy load
5.5
30.8
AWG8 (8)
M5
3.0
50 A
Light load
7.5
37.0
AWG6 (14)
60 A
3G3MX2-A2075-V1
Heavy load
7.5
39.6
AWG6 (14)
M5
3.0
60 A
Light load
11
48.0
AWG6 (14)
75 A
3G3MX2-A2110-V1
Heavy load
11
57.1
AWG4 (22)
M6
3.9 to 5.1
100 A
Light load
15
68.0
AWG4 (22)
100 A
3G3MX2-A2150-V1
Heavy load
15
62.6
AWG4 (22)
M8
5.9 to 8.8
100 A
Light load
18.5
72.0
AWG2 (38)
100 A
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...