![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 133](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918133.webp)
3 - 25
3 Operation and Test Run
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
3-4 Ope
rat
ion
Item
s fo
r T
est
Run
3
Rotate the motor with no-load (in a state not connected to the mechanical system) via the Digital Oper-
ator.
z
Forward/reverse rotation via Digital Operator
Follow the steps below to the motor in the forward or reverse rotation.
(1) Set the Output Frequency Setting/Monitor (F001).
It is recommended to initially set this to approximately 10 Hz or slower for safety reasons
(Factory default: F001 = 6.00).
(2) Set the RUN Direction Selection (F004).
In the RUN Direction Selection (F004), select 00 (Forward) or 01 (Reverse).
Press the Mode key for 3 seconds or more to display the data of Output Frequency Monitor
(d001).
Make sure that the displayed value is 0.00 (Hz).
(3) Press the RUN key.
The motor starts rotating with the RUN LED lit.
(4) Check that there is no problem with the output frequency, motor rotation direction or
inveter operation displayed on the Digital Operator.
For the rotation direction of motor, refer to the explanation for the RUN Direction Monitor
(d003).
z
Stopping Motor
After rotating the motor with no-load in the forward or reverse rotation via the Digital Operator, press
the STOP/RESET key
. The motor stops rotating.
No-load Run
Parameter No.
Function name
Data range
Default data
Unit
F001
Output Frequency Setting/
Monitor
0.00, Starting Frequency to
1st Maximum Frequency
6.0
Hz
F004
RUN Direction Selection
00: Forward
01: Reverse
00
−
d001
Output Frequency Monitor 0.00 to 99.99
100.0 to 400.0
−
Hz
d003
RUN Direction Monitor
F: Forward
o: Stop
r: Reverse
−
−
Key
Data display example
Description
Press the Mode key for 3 seconds or more to display the d001
data “0.00”.
Press the RUN key.
The RUN command LED indicator lights and the frequency refer-
ence monitor value is displayed on the data display.
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...