6 Vector Control and Applied Functions
6 - 16
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-4
Torque Control
The 3G3MX2-V1 Series Inverter provides the torque control mode.
This section describes the torque control settings and functions.
The inverter provides torque control that controls the output torque of the motor.
• This function is enabled when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless vec-
tor control).
• To use torque control, allocate one of the Multi-function Input S1 to S7 Selection (C001 to C007) to
52 (ATR: Torque reference input permission).
The torque reference input is enabled when the terminal ATR is input.
• The torque reference input source can be selected in the Torque Reference Input Selection (P033).
Select whether to input the torque reference in the Torque Reference Setting (P034), or via an analog
input terminal.
When the torque reference is input via an analog input terminal, the torque range is 0 to 200% at 0 to
10 V (4 to 20 mA).
• The torque control function regards the torque reference value equivalent to the rated output current
of the inverter as 100%.
To convert it to the rated motor torque ratio, use the following formula:
• Because, under torque control, the speed of the inverter is determined by the balance between
torque and load, to prevent the inverter from going out of control, set the Speed Limit Value in Torque
Control (Forward/Reverse) (P039 and P040).
• Switching between normal frequency control to torque control may cause a shock on the motor oper-
ation because the control is different. To reduce the shock during switching, adjust the Speed/Torque
Switching Time (P041).
Increasing the set time reduces the shock.
6-4-1
Torque Control Settings
Rated motor torque ratio = [Torque reference set value]
×
[Rated output current of inverter] / [Rated
motor current]
Parameter
No.
Function name
Data
Default
data
Unit
P033
Torque Reference Input
Selection
00:
Terminal FV (10 V = 200%)
00
−
01:
Terminal FI (20 mA = 200%)
03:
Digital Operator (P034 setting)
06:
Option (No applicable Option)
P034
Torque Reference Setting
0. to 200.
(Torque reference when P033 = 03)
0.
%
P039
Speed Limit Value in Torque
Control (Forward)
0.00 to 99.99/100.0 to 120.0
0.00
Hz
P040
Speed Limit Value in Torque
Control (Reverse)
0.00 to 99.99/100.0 to 120.0
0.00
Hz
P041
Speed/Torque Switching
Time
0. to 1000.
0.
ms
C001 to
C007
Multi-function Input S1 to
S7 Selection
52:
ATR (Torque reference input permis-
sion)
−
−
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...