8-9 Mo
db
us Co
mm
un
icatio
n Dat
a L
ist
s
8
8-9
-5 2nd C
ontrol Register Nu
mber List
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
2203 hex
2202 hex
2nd Base Frequency
A203
R/W
300 to 2nd Maximum
Frequency
0.1 [Hz]
P. 5-21
2204 hex
2203 hex
2nd Maximum Fre-
quency
A204
R/W
2nd Base Frequency to
4000
*1
*1. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
0.1 [Hz]
P. 5-21
2205 to
2215 hex
−
Reserved
−
−
−
−
2216 hex
2215 hex
2nd Multi-step
Speed Reference 0
A220
(HIGH)
R/W 0
Starting Frequency to
2nd Maximum Fre-
quency
0.01
[Hz]
*2
*2. When the PID function is enabled, the data unit differs between read and write operations.
Set parameter values in units of 0.01 Hz for writing and in units of 0.1% (as a percentage of the maximum fre-
quency) for reading.
P. 5-49
2217 hex
2216 hex
A220
(LOW)
R/W
2218 to
223A hex
−
Reserved
−
−
−
−
−
223B hex
223A hex
2nd Torque Boost
Selection
A241
R/W
00:
Manual torque
boost
−
P. 5-60
01:
Automatic torque
boost
223C hex
223B hex
2nd Manual Torque
Boost Voltage
A242
R/W 0 to 200
0.1 [%]
223D hex
223C hex
2nd Manual Torque
Boost Frequency
A243
R/W 0 to 500
0.1 [%]
223E hex
223D hex
2nd Control Method
A244
R/W
00:
Constant torque
characteristics
−
P. 5-9
P. 6-3
01:
Reduced torque
characteristics
02:
Free V/f setting
03:
Sensorless vector
control
*3
*3. Sensorless vector control can be set in the heavy load mode only.
223F hex
223E hex
2nd Output Voltage
Gain
A245
R/W 20 to 100
1 [%]
P. 7-41
2240 hex
223F hex
2nd Automatic
Torque Boost
Voltage
Compensation Gain
A246
R/W 0 to 255
1 [%]
P. 5-60
2241 hex
2240 hex
2nd Automatic
Torque Boost Slip
Compensation Gain
A247
R/W 0 to 255
1 [%]
2242 to
224E hex
−
Reserved
−
−
−
−
−
224F hex
224E hex
2nd Frequency
Upper Limit
A261
(HIGH)
R/W 0
2nd Frequency Lower
Limit to 2nd Maximum
Frequency
0.01
[Hz]
P. 5-31
2250 hex
224F hex
A261
(LOW)
R/W
2251 hex
2250 hex
2nd Frequency
Lower Limit
A262
(HIGH)
R/W 0
Starting Frequency to
2nd Frequency Upper
Limit
0.01
[Hz]
2252 hex
2251 hex
A262
(LOW)
R/W
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...