10-1 Multi-function Output Selection
5-10 Multi-function Output Settings
• You can allocate the functions shown in the following table to the multi-function output P1 and P2
terminals, and the multi-function relay output (MA, MB) terminals.
• This section describes seven types of primary functions. For other functions, refer to
7-2
Multi-function Input/Output Functions
on page 7-18.
• Set the functions in the Multi-function Output P1/P2 Selection (C021/C022) and the Multi-function
Relay Output (MA, MB) Function Selection (C026) to use them.
• The multi-function output P1 and P2 terminals are for open collector output and the multi-function
relay output (MA, MB) terminals are for relay output.
• The default data of Multi-function Relay Output (MA, MB) Function Selection (C026) is 05 (AL: Alarm
signal). Therefore, the Multi-function Relay Output (MA, MB) Operation Selection (C036) is set to 01
(NC: NC contact) by default.
This manual describes each function with the Multi-function Output Operation Selection set to 00
(NO: NO contact). Note that the operations of the Multi-function Relay Output (MA, MB) are reversed.
• Set the multi-function output P1/P2 terminals and the multi-function relay output (MA, MB) terminals
to either NO (NO contact) or NC (NC contact) individually.
• This manual describes each function with the Multi-function Output Operation Selection set to 00
(NO: NO contact). Note that the signal operations are reversed when you set them to 01 (NC: NC
contact).
5-10-1 Multi-function Output Selection
Parameter
No.
Data
Function name
Reference item
Page
Multi-function
Output P1/P2
Selection
(C021/C022)
Multi-function
Relay Output
(MA, MB)
Function
Selection
(C026)
00
RUN:
Signal during RUN
Signal during RUN
P. 5-56
01
FA1:
Constant speed arrival signal Constant speed arrival signal
P. 5-57
05
AL:
Alarm signal
Alarm signal
P. 5-57
21
ZS:
0 Hz detection signal
0 Hz detection signal
P. 5-58
50
IRDY:
Operation ready
Operation ready signal
P. 5-59
51
FWR:
Forward run signal
Forward run signal
P. 5-59
52
RVR:
Reverse run signal
Reverse run signal
P. 5-59
5-10-2 Multi-function Output Operation Selection
Parameter
No.
Function name
Data
Default
data
Unit
C031
Multi-function Output P1
Operation Selection
00:
NO (NO contact)
00
−
C032
Multi-function Output P2
Operation Selection
01:
NC (NC contact)
C036
Multi-function Relay Output
(MA, MB) Operation
Selection
00:
NO contact between MA and MC,
NC contact between MB and MC
01
−
01:
NC contact between MA and MC,
NO contact between MB and MC
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...