10 Troubleshooting
10 - 4
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
10-1-2 Alarm Code List
Name
Description
Alarm
code
Check and remedy
Reference
page
Overcurrent
protection
If the brake is applied to
the motor, or if motor is
rapidly accelerated or
decelerated, a large cur-
rent will flow through the
inverter, which results in a
fault. Therefore, the protec-
tion circuit is activated at
approximately 200% of the
inverter rated output cur-
rent, and the inverter trips.
During
constant
speed
E01.
Is there any rapid load fluctua-
tion?
• Eliminate load fluctuation.
Is there any output short-circuit?
• Check the output wiring.
Is there any ground fault?
• Check the output wiring and
the motor.
P. 5-33
P. 5-60
P. 6-61
P. 7-76
P. 7-79
During
Deceler-
ation
E02.
Is there any rapid deceleration?
• Increase the deceleration
time.
During
Acceler-
ation
E03.
Is there any rapid acceleration?
• Increase the acceleration
time.
Is the motor locked?
• Check the motor and wiring.
Is the torque boost too high?
• Decrease the torque boost
setting.
• If a PM motor is in use, is the
motor set and adjusted prop-
erly?
Others
E04.
Is the DC injection braking power
too high?
• Decrease the braking power.
P. 7-91
Overload pro-
tection
*1
*1. The inverter will not accept the reset command until approximately 10 seconds after the occurrence of a trip
(specifically, after activation of the protective function).
This function monitors the inverter
output current and, if the built-in elec-
tronic thermal function detects a
motor overload, causes the inverter to
trip.
If the Motor Electronic Thermal Selec-
tion (b910) is set to separate the over-
load protection for the motor and for
the inverter, this function serves as
the motor overload protection.
E05.
Is the load too heavy?
• Reduce the load rate.
Is the thermal level setting
(b012/b212) correct?
• Adjust the thermal level to an
appropriate level.
P. 5-16
P. 5-60
P. 6-61
P. 7-73
P. 7-76
Braking resis-
tor overload
protection
The inverter trips if the usage rate of
the regenerative braking circuit
exceeds the value set in b090.
E06.
Is there any rapid deceleration?
• Increase the deceleration
time.
Is the operation cycle time too
short?
• Increase the operation cycle
time.
P. 5-33
P. 5-65
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...