1 - 23
1 Overview
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
1-
4 Rest
riction
s
1
1-4
Restrictions
Selecting the PM motor mode disables the following functions.
• 2nd control
• Torque control and torque limit functions
• Encoder feedback function
• Induction motor control function
• Automatic Voltage Regulator (AVR)
• Dual rating function (Heavy/Light load mode)
• Simple position control function, Energy-saving control, Brake control, Overcurrent suppression func-
tion, Jogging function, etc.
Therefore, unavailable parameters and the selection functions that cannot be selected in parameters,
are not displayed on the Digital Operator. In addition, for some parameters, the default data are
changed.
For details, refer to
6-8 PM Motor Mode
on page 6-53.
Selecting the light load mode disables the following control.
• Sensorless vector control
Therefore, functions associated with this control such as auto-tuning/motor parameter setting, torque
control, and torque limit functions are unavailable.
In addition, switching from the heavy load mode to the light load mode causes the inverter rated current
and overload detection level to be changed, which also changes the default data and setting ranges of
some parameters.
For details, refer to
5-2-2 Heavy Load/Light Load Selection
on page 5-12.
Precautions for Correct Use
• Derating of the rated output current of the inverter may be required depending on the
heavy/light load mode selection, operating ambient temperature, side-by-side installation,
and carrier frequency setting.
Use the inverter in an appropriate environment according to
A-1 Derating
on page A-2.
• In the light load (VT) mode, the PM motor mode cannot be used. Switching from the light load
(VT) mode to the PM motor mode causes the rated current and overload detection settings to
be changed to those for the heavy load mode.
Derating of the rated output current of the inverter may be required when a high carrier frequency is set,
depending on the heavy/light load mode selection and operating temperature.
Use the inverter in an appropriate environment according to
A-1 Derating
on page A-2.
Restriction on PM Motor Mode
Restriction on Light Load (VT) Mode
Carrier Frequency Setting and Derating of Rated Output Current
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...