7 - 29
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-3 A
n
alo
g
I/O Setting
s
7
7-3
-7 T
erminal AM (Analog Output)
The terminal AM provides an analog output of 0 to 10 VDC.
The digital terminal AM on the control circuit terminal block enables the monitoring of the output fre-
quency and the output current.
Select the signal you want to output from the following table.
7-3-7
Terminal AM (Analog Output)
AM Selection
Parameter
No.
Function
name
Data
Description
Full-scale value
C028
AM
Selection
00
Output frequency
*1
*2
*1. 07 (LAD frequency) represents the frequency commanded by the inverter and is equivalent of the Output Fre-
quency Monitor (d001) value. 00 (Output frequency) represents a frequency value that takes into account the
aspects of vector control compensation (such as sensorless vector control) and even stabilization control.
When set to 00 (Output frequency), the parameter may produce an output that appears to be unstable at low
speeds, for example, when decelerating due to the overload limit function. In this case, set it to 07 (LAD fre-
quency) to obtain a stable output.
*2. Setting the Pulse Train Input RP Selection (P003) to 01 (Feedback pulse) causes the inverter to output the
frequency displayed in the Real Frequency Monitor (d008).
0 to Maximum frequency [Hz]
01
Output current
0 to 200%
02
Output torque
*3
*3. This setting is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless vector con-
trol). When A044/A244 is not set to 03, the inverter does not produce output because it remains at 0 V.
0 to 200%
04
Output voltage
0 to 133%
(Example: For 200-V class, 7.5 V at
200 V)
05
Input power
0 to 200%
06
Electronic thermal load rate
0 to 100%
07
LAD frequency
*1
0 to Maximum frequency [Hz]
10
Cooling fin temperature
0 to 200°C (Outputs 0°C for 0°C or
lower)
11
Output torque (signed)
*3
0 to 200%
*4
*4. The specifications of the output torque (signed) are as follows.
13
DriveProgramming (YA(1))
Use DriveProgramming to set this
function.
(0.00 to 100.00%)
16
Option (No applicable Option)
−
200
100
10
5
0
AM Gain Setting (C106) = 200%
AM Gain Setting (C106) = 100%
AM Bias Setting (C109) = 50%
Torque [%]
AM output [V]
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...