![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 325](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918325.webp)
7 - 15
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
1 Mon
ito
r Mod
e
7
7-1
-28 F
ault
Monitor
1 to 6 [d
081 to 086]
Use these functions to display the fault history of the last six faults. This count value will be stored to the
inverter’s EEPROM when the power supply is turned OFF.
The latest fault history is displayed in the Fault Monitor 1 (d081).
z
Displayed items
(1)
Trip fault factor (Alarm code): Displays one of E01 to E83.
Refer to
10-1-2 Alarm Code List
on page 10-4.
(2)
Output frequency at trip [Hz]
(3)
Output current at trip [A]
The monitor value may become zero when the inverter is in a stop state (E**.1)
(4)
DC voltage between P and N in main circuit at trip [V]
The monitor value may become zero if a ground-fault trip occurs when the power supply is
turned on.
(5)
Total RUN time of inverter before trip [h]
(6)
Total power ON time of inverter before trip [h]
Displays
if there is no trip.
Use this function to display the warning code if any inconsistency is found among the set data.
The program LED “PRG” remains lit during the warning, until the inconsistent data is corrected.
For details on the warning display, refer to
10-1-4 Warning Display
on page 10-12.
Use this function to display the P-N DC voltage of the inverter (DC voltage between the P/
+
2 and N/
−
terminals of the inverter.)
During operation, the monitor value changes according to the actual DC voltage of the inverter.
7-1-28 Fault Monitor 1 to 6 [d081 to 086]
7-1-29 Warning Monitor [d090]
7-1-30 DC Voltage Monitor [d102]
Parameter
No.
Function name
Data
Default
data
Unit
d102
DC Voltage Monitor
0.0 to 999.9
1000.
−
V
(1) Fault factor
(Alarm code)
(2) Frequency (3) Current (4) DC voltage (5) Total
RUN time
(6) Total Power
ON time
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...