1 - 13
1 Overview
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
1-3 S
p
ecific
ation
s
1
1
-3-1
S
tand
ard S
pecifications
3-phase 400-V Class
Item
3-phase 400 V
Model
(3G3MX2-
-V1)
A4004
A4007
A4015
A4022
A4030
A4040
A4055
A4075
A4110
A4150
Maximum
applicable
motor
capacity
*1
*1. “Applicable motor” represents standard 3-phase motors. When using other types of motors, make sure that the
rated current of the motor does not exceed that of the inverter.
kW
CT
0.4
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
VT
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
HP
CT
1/2
1
2
3
4
5
7 1/2
10
15
20
VT
1
2
3
4
5
7 1/2
10
15
20
25
Rated out-
put capac-
ity [kVA]
380 V
CT
1.1
2.2
3.1
3.6
4.7
6.0
9.7
11.8
15.7
20.4
VT
1.3
2.6
3.5
4.5
5.7
7.3
11.5
15.1
20.4
25.0
480 V
CT
1.4
2.8
3.9
4.5
5.9
7.6
12.3
14.9
19.9
25.7
VT
1.7
3.4
4.4
5.7
7.3
9.2
14.5
19.1
25.7
31.5
Rated input voltage
3-phase 380 V
−
15% to 480 V
+
10%, 50/60 Hz
±
5%
Rated input current
[A]
CT
1.8
3.6
5.2
6.5
7.7
11.0
16.9
18.8
29.4
35.9
VT
2.1
4.3
5.9
8.1
9.4
13.3
20.0
24.0
38.0
44.0
Rated output voltage
*2
*2. The output voltage decreases as the input voltage drops.
3-phase 380 to 480 V (Less than incoming voltage)
Rated output current
[A]
CT
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18.0
24.0
31.0
VT
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23.0
31.0
38.0
Braking torque during
short-time deceleration
[%]
*3
(discharge resistor not
connected)
*3. The braking torque during capacitor feedback is the average deceleration torque applied when the motor de-
celerates in the shortest deceleration time (when stopped from 50 Hz), not the continuous regenerative torque.
The average deceleration torque varies depending on the motor loss. This value will decrease in operation over
50 Hz.
50
50
50
20
20
20
20
20
10
10
Braking
resistor
circuit
*4
*4. The usage rate of the regenerative braking function is 10%.
Regenera-
tive braking
Built-in braking resistor circuit (discharge resistor separately mounted)
Minimum
connection
resistance
[
Ω
]
180
180
180
100
100
100
70
70
70
35
Weight [kg]
1.5
1.6
1.8
1.9
1.9
2.1
3.5
3.5
4.7
5.2
Dimensions (Width
×
Height) [mm]
108
×
128
140
×
128
140
×
260
180
×
296
Dimensions (Depth)
[mm]
143.5
170.5
155
175
CT: Heavy load, VT: Light load
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...