6 Vector Control and Applied Functions
6 - 12
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-2
Torque Limit Function
Use the torque limit function to limit the output torque of motor.
This function is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless
vector control).
• The Torque Limit Selection (b040) provides four modes as shown below.
• Setting one of the Multi-function Input S1 to S7 Selection (C001 to C007) to 40 (TL: Torque limit
enabled) enables the torque limit function set in the Torque Limit Selection (b040) only when the ter-
minal TL is input.
When this terminal is reset, the torque limit setting is disabled and the inverter uses the maximum
value (200%) as the torque limit value.
When the Torque limit enabled (TL) function is not allocated to any of the multi-function input termi-
nals, the torque limit function set in the Torque Limit Selection (b040) is always enabled.
• The torque limit function regards the torque value equivalent to the rated output current of the inverter
as 100%.
To convert it to the rated motor torque ratio, use the following formula:
• When the Multi-function Output P1/P2 Selection (C021/C022), or Multi-function Relay Output (MA,
MB) Function Selection (C026) is set to 10 (TRQ: Torque limit), you can check if the torque limit func-
tion is activated with the status of the torque limit signal.
6-2-1
Torque Limit Function Settings
Mode
Description
Four-quadrant separate
setting mode (b040 = 00)
Use this mode to set the four-quadrant (Forward Power Running, Reverse Regen-
eration, Reverse Power Running, and Forward Regeneration) torque limits in the
Torque Limit 1 to 4 (b041 to b044).
Terminal switching mode
(b040 = 01)
Use this mode to switch the Torque Limit 1 to 4 (b041 to b044) setting based on
the combination of the torque limit switching functions 1 and 2 (TRQ1 and TRQ2)
allocated to multi-function input terminals.
The selected torque limit value is enabled for all RUN modes.
Analog input mode
(b040 = 02)
Use this mode to set the torque limit value based on the analog voltage applied to
the terminal FV of the control terminal block.
0 to 10 V is equivalent to the torque limit value of 0% to 200%. The torque limit
value set via the analog input terminal is enabled for all RUN modes.
Option mode (b040 = 03)
Use this mode to set the torque limit value from optional equipment. At present,
OMRON provides no options that support this mode.
Rated motor torque ratio = [Torque limit set value]
×
[Rated output current of Inverter] / [Rated
motor current]
Parameter No.
Function name
Data
Default
data
Unit
b040
Torque Limit Selection
00:
Four-quadrant separate setting
00
−
01:
Terminal switching
02:
Analog voltage input
03:
Option (No applicable Option)
b041
Torque Limit 1
(Four-quadrant Mode For-
ward Power Running)
0. to 200.
255: no (Torque limit disabled)
Forward Power Running torque limit
when b040 = 00
200.
%
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...