unction
This inverter can be configured to output a control signal from the multi-function output terminal if the
PID feedback value falls out of the setting range.
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or the Multi-function Relay Output (MA,
MB) Function Selection (C026) to 31 (FBV).
Set the Feedback Comparison Signal Off/On Level (C052/C053) in units of percentage as 100% of the
1st/2nd Maximum Frequency (A004/A204).
When the RUN command is input by the PID function, the FBV output starts with the ON state, indepen-
dent of the Off/On level of the feedback comparison signal.
Use this parameter to monitor the PID feedback value in units of percentage as 100% of the maximum
frequency.
The monitor value is displayed as a product of the feedback value and the PID Scale (A075).
d004 = Feedback value
×
PID Scale (A075)
Use this function to clear the integral value of PID operation.
Allocate the Multi-function Input S1 to S7 Selection (C001 to C007) to 24 (PIDC).
The integral value is cleared every time the PIDC terminal is turned ON.
Never turn ON the PIDC terminal during PID operation. Doing so may cause an overcurrent trip. Be
sure to deactivate the PID operation before you turn ON the PIDC terminal.
This inverter can be configured to shut off its output when the PID Sleep Operation Delay Time (A157)
elapsed since the PID output reached the PID Sleep Operation Level (A156) or lower. The stop method
(deceleration stop/free-run stop) depends on the Stop Selection (b091) setting. The PID sleep function
will not be activated if the normal PID output is restored within the PID Sleep Operation Delay Time.
Even if the PID disabled signal is input by the PID function, the inverter will shut off its output when the
time set in A157 elapsed since the frequency reference value reached the level set in A156 or lower.
The stop method depends on the b091 setting.
Feedback Comparison Signal
PID Feedback Value Monitor (d004)
PID Integral Reset (PIDC)
PID Sleep Function
ON
OFF
OFF
ON
Feedback Comparison Signal Off Level
(C052)
PID feedback
FW input
Feedback Comparison Signal On Level
(C053)
Time
FBV output
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...