![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 596](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918596.webp)
12 Options
12 - 48
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
12-15DeviceNet Communications Unit
(Model: 3G3AX-MX2-DRT-E)
12-15-1 Specifications
Item
Specifications
Mounting
Unit type
MX2 Series DeviceNet Communications Unit
Model
3G3AX-MX2-DRT-E
Weight
100 g max. (Shipping weight: Approx. 170 g)
Environment
Operating ambient
temperature
−
10 to 50°C (with no freezing or condensation)
Operating ambient
humidity
20% to 90%
Storage ambient
temperature
−
20 to 65°C (with no freezing or condensation)
Vibration resistance
5.9 m/s
2
(0.6 G), 10 to 55 Hz
Dielectric strength
500 VAC (between isolated circuits)
Location
At a maximum altitude of 1,000 m, indoors (without corrosive
gases or dust)
Compliance with EMC and
electrical safety standards
EN61800-3: 2004 (2004/108/EC) Second environment, Category C3
EN61800-5-1: 2007(2006/95/EC) SELV
UL/cUL standard
UL508
Enclosure rating
IP20
DeviceNet
interface
Communications protocol
DeviceNet
Certification
DeviceNet conformance test
DeviceNet profile
AC drive (0
×
02)
Supported connections
Remote I/O: Master-Slave connection
Poll
Explicit message
Conforming to the DeviceNet specifications
Communications power
supply
11 to 25 VDC (50 mA max., typ. 20 mA)
Unit device address range Node address MAC ID 0 to 63, set via inverter parameter P192 or
rotary switch
Supported baud rates
125, 250, or 500 kbps
Automatic baud rate detection by Master Unit
DeviceNet
configuration
Default connection path
Supported, set via inverter parameter P046
Supported assemblies
Basic Speed I/O (Output assembly 20, Input assembly 70)
Extended Speed I/O (21, 71)
Extended Speed and Torque Control (123, 173)
Special I/O (100, 150)
Extended Control I/O (101, 151)
Extended Control I/O and Multi-function Input Monitor (101, 153)
Flexible format (139, 159)
Extended Speed and Acceleration Control (110, 111)
In case the DeviceNet Master Unit is configured using user
allocation, only the input/output pairs can be configured.
EDS file
Dependent on inverter model
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...