2 Design
2 - 16
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
The diagram below shows the configuration of the inverter main circuit. The function of each peripheral
component is also described.
Main Circuit Configuration Diagram
Name
Function
(a) (b) (c)
Refer to
Recommended Cable Size, Wiring
Device, and Crimp Terminal
on page 2-19.
(d) AC reactor
This is used as a harmonic suppression mea-
sure. It also helps improve the power factor. The
AC reactor is used when the power supply volt-
age unbalance factor is 3% or more, the inverter
capacity is 500 kVA or more, or rapid change in
the power supply voltage occurs to reduce its
effect.
(e) Input noise filter
This filter reduces the conductive noise gener-
ated in the inverter and transmitted via wires.
Connect it to the primary side (input side) of the
inverter.
(f) Radio noise filter
The inverter in operation may cause noise
through the power supply wiring etc., which
could affect radio receivers or other equipment
nearby. This filter reduces such noise (radiated
noise).
(g) DC reactor
This reactor helps suppress harmonics gener-
ated by the inverter.
(h) Braking resistor
(i) Regenerative braking unit
These increase the amount of regenerative
energy absorption when the inverter applies
motor braking and are used to decrease the the
speed of an elevator or load with a large
moment of inertia.
All models of the 3G3MX2-V1 Series Inverter
have built-in regenerative braking processing
circuit.
The Regenerative Braking Unit is necessary
only if a large braking torque is required and the
built-in regenerative braking processing circuit
cannot allow it.
(j) Output noise filter
This filter is installed between the inverter and
the motor to reduce the radiated noise emitted
from cables. It is used to reduce radio and tele-
vision interference and prevent meter and sen-
sor malfunction.
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(h)
R S T
+
1
P/
+
2
RB
N/
−
U V W
(j)
(f)
M
MC
MCCB
(a)
(b)
Power supply
Inverter
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...