![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 360](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918360.webp)
7 Other Functions
7 - 50
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
This function automatically adjusts the inverter output power during constant speed operation to the
minimum level. It is suitable for fan, pump, or other load that reduced torque characteristics.
To perform energy-saving operation using this function, set the Operation Mode Selection (A085) to 01
(Energy-saving operation).
You can adjust the response and accuracy of the function in the Energy-saving Response/Accuracy
Adjustment (A086).
Because this function controls the output power to the minimum necessary level, the motor may stall if
the rapid load fluctuation, such as impact load, occurs, which may result in an overcurrent trip.
The automatic energy-saving operation function may not work sufficiently when the frequency refer-
ence source is set to Control circuit terminal block (Analog input). In this case, set the Analog Input Fil-
ter (A016) to 31 (500 ms).
Use this function to drive a system subject to a large load inertia moment during acceleration and
deceleration with the inverter and during constant speed operation with a commercial power supply,
respectively.
Allocate the Multi-function Input S1 to S7 Selection (C001 to C007) to 14 (CS).
Follow the sequence diagram given below to switch among the terminals MC1 to MC3, FW, and CS.
When the terminal CS turns ON, the inverter shuts off its output and the motor falls in a free-run state.
Follow the sequence diagram given below to switch among the terminals MC1 to MC3 and, with the
RUN command and CS input ON, turn the terminal CS from ON to OFF. Then, when the Restart
Standby Time (b003) elapses, the inverter starts accelerating with its frequency matched with the motor
rotation speed during free run (“frequency matching restart”). However, the inverter may restart at 0 Hz
in any of the following cases:
• The motor rotation speed is equal to or lower than 1/2 of the base frequency.
• The motor induction voltage decays quickly and the motor rotation speed cannot be detected.
• The motor rotation speed drops to the Frequency Matching Lower Limit Frequency (b007) or lower.
7-5-13 Automatic Energy-saving Operation Function
Parameter
No.
Function name
Data
Default
data
Unit
A085
Operation Mode
Selection
00:
Normal operation
00
−
01:
Energy-saving operation
Parameter
No.
Function name
Data
Default
data
Unit
A086
Energy-saving
Response/Accuracy
Adjustment
0.0 to 100.0
(Response: Slow to Fast)
(Accuracy: High to Low)
50.0
%
7-5-14 Commercial Switching (CS)
Parameter
No.
Function name
Data
Default
data
Unit
C001 to
C007
Multi-function Input S1
to S7 Selection
14:
CS (Commercial switching)
−
−
Related functions
b003, b007
Switching from Inverter Operation to Commercial Power Supply Operation
Switching from Commercial Power Supply Operation to Inverter Operation
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...