6 Vector Control and Applied Functions
6 - 62
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
z
PM Motor Parameter Ld (H107)
Set the d-axis inductance (in mH) of the motor in Y-connection.
Alternatively, set 50% of the phase-to-phase inductance of the motor measured with an LCR meter.
Be sure to set this parameter so that Ld is equal to or less than Lq. Not doing so may result in an
overload.
z
PM Motor Parameter Lq (H108)
Set the q-axis inductance (in mH) of the motor in Y-connection.
Alternatively, set 50% of the phase-to-phase inductance of the motor measured with an LCR meter.
Be sure to set this parameter so that Ld is equal to or less than Lq.
z
PM Motor Parameter Ke (H109)
Set the inductive voltage parameter of your PM motor in Vp/(rad/s).
This value must be set in “Vp/(rad/s).” If the datasheet provides this parameter in a different unit, you
need to perform unit conversion.
z
PM Motor Parameter J (H110)
Calculate the motor-shaft conversion of the moment of load inertia, add the moment of inertia of the
motor to it, and set the sum.
z
Motor Cable Length (b033)
Set the cable length from the inverter to the motor.
To maximize the performance of the inverter, set the cable length to 20 m or shorter.
Example
If the inductive voltage parameter for one phase is 10 [mV/r/min], the set value can be calculated as
follows:
10 [mV/r/min] =
(10/1000 [V])
×
(
√
2)
×
(60 [s]) / ((2
π
×
4 [pole] / 2) [rad]) =
0.0675 [Vp/(rad/s)]
Parameter
No.
Function name
Data
Default
data
Unit
A003
1st Base Frequency
30.0 to 1st Maximum Frequency (A004)
60.0
Hz
A004
1st Maximum Frequency
1st Base Frequency (A003) to 400.0
60.0
Hz
b033
Motor Cable Length
5. to 20.
10.
m
A082
1st Motor Rated Voltage
Selection
200-V class: 200/215/220/230/240
200 or 400
V
400-V class: 380/400/415/440/460/480
H102
PM Motor Parameter
Selection
00:
Standard PM motor parameter
00
−
02:
Auto-tuning parameter
H103
PM Motor Capacity
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5
Maximum
applicable
motor
capacity
kW
H104
PM Motor Pole Number
2/4/6/8
10 to 48: Do not set.
Dependent
on capacity
pole
H105
PM Motor Rated Current
0.20
×
Rated current to 1.00
×
Rated current
Rated cur-
rent
A
b012
1st Electronic Thermal
Level
0.20
×
Rated current to 1.00
×
Rated current
Rated cur-
rent
A
H106
PM Motor Parameter R
0.001 to 65.53
Dependent
on capacity
Ω
H107
PM Motor Parameter Ld
0.01 to 655.3
Dependent
on capacity
mH
H108
PM Motor Parameter Lq
0.01 to 655.3
Dependent
on capacity
mH
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...