4 Parameter List
4 - 16
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
*1. The default data was changed from the previous model.
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Setting
during
RUN
Changes
during
RUN
Unit
Page
Overlo
ad limit,
o
vercurrent protecti
on
b021
1st Overload Limit
Selection
00: Disabled
01
Disabled
Enabled
−
P. 7-76
01: Enabled during acceleration
and constant speed
b221
2nd Overload Limit
Selection
02: Enabled
during
constant
speed
01
Disabled
Enabled
03: Enabled during acceleration
and constant speed (Accel-
erated during regeneration)
b022
1st Overload Limit
Level
0.20
×
Rated current to 2.00
×
Rated current (Heavy load)
0.20
×
Rated current to 1.50
×
Rated current (Light load)
Rated
current
×
1.50
(Heavy)
1.20
(Light)
Disabled
Enabled
A
b222
2nd Overload Limit
Level
Disabled
Enabled
A
b023
1st Overload Limit
Parameter
0.1 to 999.9
1000. to 3000.
1.0
Disabled
Enabled
s
b223
2nd Overload Limit
Parameter
1.0
Disabled
Enabled
b024
1st Overload Limit
Selection 2
00: Disabled
01
Disabled
Enabled
−
01: Enabled during acceleration
and constant speed
02: Enabled
during
constant
speed
03: Enabled during acceleration
and constant speed (Accel-
erated during regeneration)
b025
1st Overload Limit
Level 2
0.20
×
Rated current to 2.00
×
Rated current (Heavy load)
0.20
×
Rated current to 1.50
×
Rated current (Light load)
Rated
current
×
1.50
(Heavy)
1.20
(Light)
Disabled
Enabled
A
b026
1st Overload Limit
Parameter 2
0.1 to 999.9
1000. to 3000.
1.0
Disabled
Enabled
s
b027
Overcurrent Sup-
pression Selection
00: Disabled
01
*1
Disabled
Enabled
−
P. 7-79
01: Enabled
02: Enabled (at reduced voltage
startup)
b028
Frequency Pull-in
Restart Level
0.20
×
Rated current to 2.00
×
Rated current (Heavy load)
0.20
×
Rated current to 1.50
×
Rated current (Light load)
Rated cur-
rent of
inverter
Disabled
Enabled
A
P. 5-45
P. 7-61
b029
Frequency Pull-in
Restart Parameter
0.1 to 999.9
1000. to 3000.
0.5
Disabled
Enabled
s
b030
Starting Frequency
Selection at
Frequency Pull-in
Restart
00: Frequency at interruption
00
Disabled
Enabled
−
01: Maximum
frequency
02: Set
frequency
(Frequency
reference)
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...