7 - 5
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
1 Mon
ito
r Mod
e
7
7-1
-3 RU
N Direction
Monito
r [d003]
Use this function to display the RUN direction of the inverter.
The RUN LED is lit during inverter operation (forward/reverse RUN).
Generally, the forward rotation is defined as the direction in which the motor rotates counterclockwise when
viewed from the shaft.
Use this function to monitor the PID feedback value when the PID Selection (A071) is set to 01
(Enabled) or 02 (Reverse output enabled).
The monitor value is displayed in units of percentage as 100% of the 1st/2nd Maximum Frequency
(A004/A204) and can be converted by setting the PID Scale (A075) as follows.
d004 = Feedback value [%]
×
PID Scale (A075)
Use this function to display the input status of each multi-function input terminal, based on whether the
corresponding 7-segment LED is lit or not lit.
The terminal for which the built-in CPU detected the input is indicated as ON. Note that this is indepen-
dent of the NO/NC contact setting for each multi-function input terminal.
• When the input terminal response time function is enabled, the inverter cannot display the input sta-
tus immediately. (Refer to
5-9-3 Input Terminal Response Time
on page 5-48.)
• The terminal S5 remains OFF and cannot be monitored when Multi-function Input S5 Selection
(C005) is allocated to 19 (TH: PTC thermistor thermal protection).
7-1-3
RUN Direction Monitor [d003]
Parameter
No.
Function name
Data
Default
data
Unit
d003
RUN Direction Monitor
F : Forward
−
−
o : Stop
r : Reverse
7-1-4
PID Feedback Value Monitor [d004]
Parameter
No.
Function name
Data
Default
data
Unit
d004
PID Feedback Value
Monitor
0.00 to 99.99 (Displayed in increments of 0.01)
−
−
100.0 to 999.9 (Displayed in increments of 0.1)
1000. to 9999. (Displayed in increments of 1)
1000 (Displayed in increments of 10)
A075
PID Scale
0.01 to 99.99 (Set in increments of 0.01)
1.00
time
Related functions
A071, A075
7-1-5
Multi-function Input Monitor [d005]
(Example) Multi-function input terminals S7, S2, and S1
: ON
Multi-function input terminals S6, S5, S4, and S3
: OFF
Forward
ON
OFF
S7 S6 S5 S4 S3 S2 S1
(ON) (OFF)(OFF)(OFF)(OFF)(ON) (ON)
Display
: Lit
: Not lit
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...