Overtorque/Undertorque Function
Use this function to detect that the estimated motor output torque value exceeded the set level and out-
put the overtorque signal.
• This function is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless
vector control).
• To enable the detection of the overtorque/undertorque state, set the Multi-function Output P1/P2
Selection (C021/C022), or Multi-function Relay Output (MA, MB) Function Selection (C026), to 07
(OTQ: Overtorque/Undertorque signal).
• The overtorque/undertorque function regards the torque level equivalent to the rated output current of
the inverter as 100%.
To convert it to the rated motor torque ratio, use the following formula:
• Use this function to detect the brake release signal of an elevator, or if the load applied to the load
machine is abnormally high.
6-3-1
Overtorque/Undertorque Function Settings
Rated motor torque ratio = [Overtorque/Undertorque level set value]
×
[Rated output current of
Inverter] / [Rated motor current]
Parameter
No.
Function name
Data
Default
data
Unit
C054
Overtorque/Undertorque
Selection
00:
Overtorque
00
−
01:
Undertorque
C055
Overtorque/Undertorque
Level
(Forward Power Running)
0. to 200.
OTQ signal output level during Forward
Power Running
100.
%
C056
Overtorque/Undertorque
Level
(Reverse Regeneration)
0. to 200.
OTQ signal output level during Reverse
Regeneration
100.
%
C057
Overtorque/Undertorque
Level
(Reverse Power Running)
0. to 200.
OTQ signal output level during Reverse
Power Running
100.
%
C058
Overtorque/Undertorque
Level
(Forward Regeneration)
0. to 200.
OTQ signal output level during Forward
Regeneration
100.
%
C059
Overtorque/Undertorque
Signal Operation
00:
Enabled during acceleration/decelera-
tion and constant speed
01
−
01:
Enabled during constant speed
C021, C022
Multi-function Output P1/P2
Selection
07:
OTQ (Overtorque/Undertorque signal)
−
−
C026
Multi-function Relay Output
(MA, MB) Function Selection
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...