8 - 13
8 Communications Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
8-
5 Explan
atio
n o
f Each
Fu
nctio
n
C
ode
8
8-5
-3 W
rit
e to Coil [0
5 hex]
z
Response
*1. Broadcasting cannot be performed.
*2. Note that the holding register start address is 0011 hex, which is 1 less than the register number 0012 hex:
Register address = Register number - 1.
*3. Data as much as the number of data bytes will be transferred. In this example, the inverter sends back data
from six holding registers, which is 12 (0C hex) bytes.
Writes the ON/OFF status to a single coil. The coil status changes as shown in the table below.
You need to set the 1st RUN Command Selection (A002) to03 (Modbus communication).
The coil number for the RUN command is 0001.
z
Query
No.
Field name
Example
[hex]
1
Slave address
*1
01
2
Function code
03
3
Number of data bytes
*3
0C
4
Register data 1 (MSB)
00
5
Register data 1 (LSB)
03
6
Register data 2 (MSB)
00
7
Register data 2 (LSB)
04
8
Register data 3 (MSB)
00
9
Register data 3 (LSB)
00
10
Register data 4 (MSB)
04
11
Register data 4 (LSB)
D2
12
Register data 5 (MSB)
01
13
Register data 5 (LSB)
2C
14
Register data 6 (MSB)
0B
15
Register data 6 (LSB)
18
16
CRC-16 (MSB)
D0
17
CRC-16 (LSB)
6D
8-5-3
Write to Coil [05 hex]
Data
Coil status
OFF to ON
ON to OFF
Written data (MSB)
FF hex
00 hex
Written data (LSB)
00 hex
00 hex
Example. Issuing RUN Command to Inverter with Slave Address 1
No.
Field name
Example
[hex]
1
Slave address
*1
01
2
Function code
05
3
Coil address (MSB)
*2
00
4
Coil address (LSB)
*2
00
5
Written data (MSB)
FF
6
Written data (LSB)
00
7
CRC-16 (MSB)
8C
8
CRC-16 (LSB)
3 A
0003 hex
→
03 dec
→
E03 (Factor: Overcurrent)
0004 hex
→
4 dec (Inverter status: During accelera-
tion)
0000 04D2 hex
→
1234 dec
→
12.34 [Hz] (Fre-
quency)
012C hex
→
300 dec
→
3.00 [A] (Current)
0B18 hex
→
2840 dec
→
284.0 [V] (DC voltage)
dec: Decimal
hex: Hexadecimal
(Coil address) = (Coil number)
−
1
OFF to ON: FF00 hex
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...