1 - 15
1 Overview
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
1-3 S
p
ecific
ation
s
1
1
-3-1
S
tand
ard S
pecifications
Common Specifications
Item
Specifications
Enclosure rating
*1
Open type (IP20)
Control
Control method
Phase-to-phase sinusoidal modulation PWM
Output frequency range
*2
0.01 to 400 Hz
Frequency precision
*3
Digital command:
±
0.01% of the maximum frequency, Analog command:
±
0.2% of the maximum frequency (25
±
10
°
C)
Frequency setting
resolution
Digital setting: 0.01 Hz, Analog setting: Maximum frequency
×
1/1000
Voltage/Frequency
characteristics
V/f characteristics (constant torque, reduced torque)
Sensorless vector control, V/f control with speed feedback
Overload current rating
of inverter
Heavy load rating (CT): 150%/60 s
Light load rating (VT): 120%/60 s
Instantaneous overcur-
rent protection
200% of heavy load rating (CT) value
Acceleration/
Deceleration time
0.00 to 3600 s (line/curve arbitrary setting), 2nd acceleration/deceleration
setting provided
Carrier frequency
change range
2 to 15 kHz (Derating required)
Starting torque
200%/0.5 Hz (Sensorless vector control)
DC injection braking
Operates at operating frequency or less during deceleration via STOP
command, at set frequency or less during operation, or via external input
(level and time can be set).
Protective function
Overcurrent, Overvoltage, Undervoltage, Electronic thermal, Tempera-
ture error, Ground-fault current at power-on, Inrush current protection cir-
cuit, Overload limit, Incoming overvoltage, External trip, Memory error,
CPU error, USP error, Communication error, Overvoltage suppression
during deceleration, Power interruption protection, Emergency shutoff,
etc.
Input
signal
Frequency settings
Digital Operator
External analog input signal (variable resistor/0 to 10 VDC/4 to 20 mA),
Modbus communication
RUN/STOP command
Digital Operator
External digital input signal (3-wire input available), Modbus communica-
tion
Multi-function Input
*4
7 points (Functions can be selected from among 68)
Analog input
*5
2 points (FV terminal for voltage: 10 bits/0 to 10 V, FI terminal for current:
10 bits/4 to 20 mA)
Pulse input
1 point (RP terminal: 32 kHz max., 5 to 24 VDC)
Output sig-
nal
Multi-function output
*4
2 points (P1 and P2, Functions can be selected from among 47)
Relay output
*4
1 point (SPDT contact (MC, MA, MB), Functions can be selected from
among 47)
Analog output
(Frequency monitor)
*6
1 point (AM terminal: 10 bits for voltage, 0 to 10 V) (Frequency or current
can be selected)
Pulse output
1 point (MP terminal: 32 kHz max., 0 to 10 V)
Communi-
cations
RS-422
RJ45 connector (for Digital Operator)
RS-485
Control circuit terminal, Modbus communication
USB
USB1.1, mini-B connector
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...