6 - 57
6 Vector Control and Applied Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-8
PM Motor Mode
6
6-
8-3 Switching
to PM Motor Mod
e
To use PM motor control, you need to switch the inverter to the PM motor mode.
Follow the steps below to switch to the PM motor mode:
(1) Set the Inverter Mode Selection (b171) to 03 (PM motor).
(2) Set the Initialization Execution (b180) to 01 (Execute initialization), then press the
Enter key. Parameter initialization starts.
(3) When parameter initialization is in progress,
and
are displayed alter-
nately.
(4) When the initialization process is completed,
appears, meaning that the
inverter was switched to the PM control mode.
Precautions for Correct Use
• If b171 is set to other than 00, regardless of the settings in Initialization Selection (b084) and
Initialization Target Setting (b094), when initialization is executed with the Initialization Exe-
cution (b180) set to 01 (Execute initialization), all data (set data, fault monitor data, and
DriveProgramming data) are initialized.
However, the following parameters are not initialized: Total RUN Time Monitor (d016), Total
Power ON Time Monitor (d017), Heavy Load/Light Load Selection (b049), Initialization Data
Selection (b085), Initialization Target Setting (b094), FV/FI Adjustment (C081/C082), Therm-
istor Adjustment (C085), and Position Data at Power Off (P082).
• To return to the induction motor mode after switching to the PM motor mode, set b171 to 01
(Induction motor), then execute initialization with b180 set to 01. The inverter switches to the
induction motor mode while displaying “I-C” on the Digital Operator.
Offline auto-tuning for PM motor parameters consists of the following four steps:
• Presetting of parameters
• Auto-tuning
• Operations after auto-tuning
• Operations in case of error
1
Presetting of parameters
(1) Set the PM Motor Capacity (H103) and the PM Motor Pole Number (H104) according
to your PM motor.
6-8-3
Switching to PM Motor Mode
Parameter No.
Function name
Data
Default
data
Unit
b171
Inverter Mode Selection
00:
Selection disabled
00
−
01:
Induction motor
02:
Do not set.
*1
*1. The inverter does not provide the high-frequency mode.
03:
PM motor
b180
Initialization Execution
00:
Function disabled
00
−
01:
Execute initialization
6-8-4
Offline Auto-tuning for PM Motor Parameters
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...