7 Other Functions
7 - 6
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Use this function to display the output status of each multi-function output terminal, based on whether
the corresponding 7-segment LED is lit or not lit.
Each LED shows the output status detected by the built-in CPU. Note that this is independent of the
NO/NC contact setting for each multi-function output terminal.
Use this function to display the output frequency value that is converted based on the Frequency Con-
version Coefficient (b086).
This parameter is useful when you want to view the output frequency in a different display unit, for
example, to monitor the motor rotation speed.
d007 = Output Frequency Monitor (d001)
×
Frequency Conversion Coefficient (b086)
7-1-6
Multi-function Output Monitor [d006]
(Example) Multi-function output terminals P2 and P1
: ON
Relay output terminal MA
: OFF
7-1-7
Output Frequency Monitor (After Conversion) [d007]
(Example) To monitor the rotation speed of a 4-pole motor:
Motor rotation speed N [min
−
1] = (120
×
f [Hz]) / P [pole] = f [Hz]
×
30
Therefore, if b086 = 30.0, then, at 60 Hz, the value of this parameter is 60
×
30.0 = 1800.
Parameter
No.
Function name
Data
Default
data
Unit
d007
Output Frequency
Monitor (After
Conversion)
0.00 to 99.99 (Displayed in increments of 0.01)
−
−
100.0 to 999.9 (Displayed in increments of 0.1)
1000. to 9999. (Displayed in increments of 1)
1000 to 4000 (Displayed in increments of 10)
b086
Frequency Conversion
Coefficient
0.01 to 99.99
Set in increments of 0.01
(d007 = d001
×
b086)
1.00
−
b163
d001/d007 Data
Setting Selection
00:
Disabled
(Frequency cannot be changed in
d001/d007)
00
−
01:
Enabled
(Frequency can be changed in
d001/d007)
ON
OFF
MA P2 P1
(OFF)(ON) (ON)
Display
: Lit
: Not lit
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...