5 Basic Settings
5 - 52
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
• When the jogging function is enabled, jogging operation starts when the RUN command is input.
• To enable the jogging function, set the Multi-function Input S1 to S7 Selection (C001 to C007) to 06
(JG: Jogging).
• Then, set the frequency reference for jogging operation in the Jogging Frequency (A038).
Because, in jogging operation, the frequency reference is output without acceleration time, setting a
high jogging frequency value may cause an overload or trip error. Be sure to set a frequency value
that does not cause tripping.
• Use the Jogging Stop Selection (A039) to set the jogging stop method and whether to enable or dis-
able the jogging function during operation.
z
Disabled during operation
When the Jogging Stop Selection (A039) is set to 00, 01, or 02, jogging operation is not performed if
the FW signal turns ON first.
To perform jogging operation, turn ON the JG terminal and then turn ON the terminal FW or RV.
5-9-6
Jogging (JG)
Parameter
No.
Function name
Data
Default data
Unit
C001 to
C007
Multi-function Input S1 to S7
Selection
06:
JG (Jogging)
−
−
A038
Jogging Frequency
0.00
Starting Frequency to 9.99
6.00
Hz
A039
Jogging Stop Selection
00:
Free-running on jogging stop/Dis-
abled during operation
04
−
01:
Deceleration stop on jogging
stop/Disabled during operation
02:
DC injection braking on jogging
stop
*1
/Disabled during operation
*1. If the Jogging Stop Selection(A039) is set to 02 or 05, set the DC Injection Braking Selection (A051).
Refer to
7-9-1 DC Injection Braking (DB)
on page 7-91.
03:
Free-running on jogging
stop/Enabled during operation
04:
Deceleration stop on jogging
stop/Enabled during operation
05:
DC injection braking on jogging
stop
*1
/Enabled during operation
Jogging Operation Enabled
Jogging Operation Disabled
A038
Output
frequency
JG
FW
RV
Output
frequency
JG
FW
Inverter ignores input to JG and
continues normal operation.
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...