5 Basic Settings
5 - 50
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
• Setting the Multi-function Input S1 to S7 Selection (C001 to C007) to 02 (CF1) to 05 (CF4) enables
the selection of the multi-step speed 0 to 15.
• Use the Multi-step Speed Reference 1 to 15 (A021 to A035) to set the frequency for the multi-step
speed 1 to 15.
• Use the 1st/2nd Frequency Reference Selection (A001/A201) to set the 1st/2nd Multi-step Speed
Reference 0 (A020/A220).
Set the 1st/2nd Frequency Reference Selection (A001/A201) to 02 (Digital Operator: F001) to enable
the 1st/2nd Multi-step Speed Reference 0 (A020/A220).
If A001/A201 are set to 01 (Control circuit terminal block: Analog input), the analog input is used as
the frequency reference to set the 1st/2nd Multi-step Speed Reference 0.
• For multi-step speed binary operation, the wait time until the inverter recognizes terminal input can be
set in the Multi-step Speed/Position Determination Time (C169). This prevents the transitional status
before terminal input is recognized from being accepted.
• Input data will be determined if it remains unchanged for the time set in the Multi-step Speed/Position
Determination Time (C169). Note that setting a long determination time results in a slow input
response.
Binary Operation
Parameter
No.
Function name
Data
Default data
Unit
C001 to
C007
Multi-function Input S1 to
S7 Selection
02: CF1 (Multi-step speed setting binary 1)
−
−
03: CF2 (Multi-step speed setting binary 2)
04: CF3 (Multi-step speed setting binary 3)
05: CF4 (Multi-step speed setting binary 4)
C169
Multi-step Speed/Position
Determination Time
0. to 200. (
×
10 ms)
0.
ms
Multi-step
speed
CF4
CF3
CF2
CF1
0th
OFF
OFF
OFF
OFF
1st
ON
2nd
ON
OFF
3rd
ON
4th
ON
OFF
OFF
5th
ON
6th
ON
OFF
7th
ON
8th
ON
OFF
OFF
OFF
9th
ON
10th
ON
OFF
11th
ON
12th
ON
OFF
OFF
13th
ON
14th
ON
OFF
15th
ON
CF1
CF2
CF3
CF4
FW
Frequency from
Digital Opera-
tor or external
analog input
terminal
1st
2nd
3rd
4th
5th
6th
7th
8th
9th
10th
11th
12th
13th
14th
15th
0th
CF1
CF2
CF3
13
1
5
9
11
CF4
15
4
With determination time
(C169)
With zero determination time
(C169)
Determination time
(C169)
Frequency reference
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...