5 - 27
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-5
Frequ
ency
Referen
ce Sett
ing
s
5
5-
5-1 F
requen
cy Refer
ence Selection
To use an analog voltage input or analog current input to set the frequency reference, set the parame-
ters as shown in the table below. This enables the frequency reference input (voltage reference) or fre-
quency reference input (current directive) terminal.
If input is made to both the frequency reference input (voltage reference) and frequency reference input
(current reference) terminals, the sum of the two analog input values will be set as the inverter fre-
quency reference.
However, do not set the Multi-function Input S1 to S7 Selection (C001 to C007) to 16 (AT: Analog input
switching). The terminal AT, when set, performs switching based on whether it is ON/OFF, without add-
ing the frequency reference (voltage reference) and the frequency reference input (current reference).
The frequency reference input (current reference) cannot be input unless the set terminal AT is input.
• Frequency reference input (Voltage reference), between FV and SC: 0 o 10 VDC
• Frequency reference input (Current reference), between FI and SC: 4 to 20 mA
Note
By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
*1. If the terminal AT is not set, FV input and FI input reference values will be added.
Parameter No.
Function name
Data
Default data
Unit
A001/A201
1st/2nd Frequency
Reference Selection
02:
Digital Operator (F001)
02
−
Using an Analog Voltage Input or Analog Current Input
Parameter No.
Function name
Data
Default data
Unit
A001/A201
1st/2nd Frequency
Reference Selection
01:
Control circuit terminal block
(Analog input)
02
−
A005
FV/FI Selection
00: Switch between FV (Voltage)
and FI (Current) via terminal AT
00
−
C001 to C007
Multi-function Input
S1 to S7 Selection
Do not set C001 to C007 to 16 (AT:
Analog input switching).
*1
−
−
V
A
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...