Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-4 In
verter Co
nt
ro
l Sett
ing
s
7
7-4
-1 Car
rier F
reque
ncy
7-4
Inverter Control Settings
This section describes the carrier frequency function and the 1st/2nd control switching function, which
are related to the inverter control.
Use this function to change the carrier frequency output from the inverter in a PWM waveform.
Set a higher carrier frequency value to reduce the metallic noise generated by the motor. If the inverter
generates a large sound due to resonance with the mechanical system or motor, you can effectively
avoid the resonance by setting the carrier frequency out of the resonance frequency range.
However, this results in an increase in electrical noise or leakage current from the inverter.
• Derating of the output current may be required depending on the installation environment and the
Carrier Frequency (b083) setting. For derating of each inverter model, refer to
A-1 Derating
on page
A-2.
In the Electronic Thermal Level, set the output current value to be derated.
This setting, however, is unnecessary if the Electronic Thermal Level is already set to the derating
value or lower.
For details on the electronic thermal function, refer to
5-3-2 Electronic Thermal Function
on page
5-16.
• Be aware that adjusting the carrier frequency exceeding the allowable derating level for the output
current may cause damage or shortened life expectancy of the inverter.
• The carrier frequency for DC injection braking can be set in A059. For details, refer to
7-9-1 DC Injec-
tion Braking (DB)
on page 7-91.
• The table below shows the carrier frequency setting and its influence.
7-4-1
Carrier Frequency
Parameter
No.
Function name
Data
Default
data
Unit
b083
Carrier Frequency
Heavy load mode (b049 = 00)
2.0 to 15.0
Light load mode (b049 = 01)
2.0 to 10.0
10.0
2.0
kHz
Related functions
b089
Carrier frequency
Low
High
Noise from motor
Large
Small
Noise, leakage current
Small
Large
Torque
Slightly large
Slightly small
Carrier frequency: High
Carrier frequency: Low
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...