![Omron SYSDRIVE MX2 SERIES Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918073.webp)
2 - 13
2 Design
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
2-3
W
irin
g
2
2-
3-3 Ar
range
ment and F
unction of C
ontrol Circuit T
er
m
inal Block
Digital
Power supply
SC
Input signal
common
Common terminal for the internal
power supply, digital input, and
analog I/O terminals.
P24
Input signal
power sup-
ply
This is 24-VDC power supply for
contact input signal. For source
logic input, this terminal functions
as the common terminal.
Allowable current:
100 mA max.
PSC
Input termi-
nal power
supply
For sink logic input: Short-cir-
cuited to P24
For source logic input: Short-cir-
cuited to SC
To activate contact input via an
external power supply, remove
the short-circuit bar. For details
on the connection, refer to
Multi-function Input Terminals
and Programmable Controller
Connection
on page 2-36.
Input
Contact S7
S6
S5
S4
S3
S2
S1
Multi-
function
input
Select seven functions from
among 68 functions, and allocate
them to terminals S1 to S7.
These terminals support both the
sink logic and the source logic.
For details on the connection,
refer to
Multi-function Input Ter-
minals and Programmable Con-
troller Connection
on page 2-36.
Voltage between each
input terminal and the
terminal PSC
ON voltage: 18 V min.
OFF voltage: 3 V
max.
Allowable voltage:
27 VDC max.
Load current: 5 mA
(at 24 V)
Internal resistance:
4.7 k
Ω
S4
(GS1)
S3
(GS2)
Safety input
Turn ON the safety function
selector switch to enable this ter-
minal. This automatically config-
ures S3 and S4 as follows.
S3: GS1 (Safety input 1)
S4: GS2 (Safety input 2)
Pulse
RP
Pulse input -
A
This is pulse input for frequency
setting. This terminal accepts 5
to 24 VDC input signals. (Note
that this terminal is connected to
a different internal circuit from
the input terminal S7.)
Input pulse: 32 kHz
max.
Internal resistance:
10 k
Ω
Voltage between this
input terminal and the
terminal SC:
5 to 24 VDC
ON voltage: 4V min.
OFF voltage: 1V max.
Allowable voltage:
27 VDC max.
S7
(EB)
Pulse input -
B
Set the Multi-function Input S7
Selection (C007) to 85 (EB:
Rotation direction detection) to
enable this terminal. This is pulse
input for frequency setting. (Note
that this terminal is connected to
a different internal circuit from
the input terminal RP.)
Input pulse: 1.8 kHz
max.
Internal resistance:
4.7 k
Ω
ON voltage: 18 V min.
OFF voltage: 3 V
max.
Allowable voltage:
27 VDC max.
Load current: 5 mA
(at 24 V)
Item
Terminal
symbol
Terminal
name
Description
Specifications
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...