5 - 57
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-10 Mu
lti-fun
ctio
n
Outpu
t Setting
s
5
5-
10-5 C
onst
ant S
pe
ed Arrival Signal (F
A1)
• This signal is output when the output frequency reaches the frequency set in the Output Frequency
Setting/Monitor.
In F001, the frequency reference selected at that time is displayed.
• Allocate one of the Multi-function Output P1/P2 Selection (C021/C022), or Multi-function Relay Out-
put (MA, MB) Function Selection (C026), to 01 (FA1).
• The hysteresis of this frequency arrival signal is calculated as follows.
• If an overcurrent, overvoltage, or some other error occurs, the inverter shuts off its output and outputs
an alarm signal (AL). This is called a “trip.”
• A trip state can be canceled by resetting the inverter, by which the alarm signal is also turned OFF.
To reset the inverter, press the STOP/RESET key on the Digital Operator or turn ON the reset termi-
nal. However, you cannot reset some trip factors by using these methods. In such cases, cycle the
power supply.
• Allocate one of the Multi-function Output P1/P2 Selection (C021/C022), or Multi-function Relay Out-
put (MA, MB) Function Selection (C026), to 05 (AL).
By default, the Multi-function Relay Output (MA, MB) Function Selection (C026) is set to 05 (AL:
Alarm signal).
5-10-5 Constant Speed Arrival Signal (FA1)
ON (fon)
: Set frequency
−
1% of maximum frequency) [Hz]
OFF (foff) : Set frequency
−
2% of maximum frequency) [Hz]
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection
01:
FA1 (Constant
speed arrival signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
05
−
5-10-6 Alarm Signal (AL)
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection
05:
AL (Alarm signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
05
−
f
on
f
off
Output
frequency
Set
frequency
fon: 1% of maximum frequency
foff: 2% of maximum frequency
Example
Maximum frequency = 120 [Hz]
fon = 120
×
0.01 = 1.2 [Hz]
foff = 120
×
0.02 = 2.4 [Hz]
Set frequency = 60 [Hz]
During acceleration: FA1 is ON at 60 - 1.2 = 58.8 [Hz]
During deceleration: FA1 is OFF at 60 - 2.4 = 57.6 [Hz]
FA1
Содержание SYSDRIVE MX2 SERIES
Страница 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Страница 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 310: ...6 Vector Control and Applied Functions 6 68 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 516: ...9 Overview of DriveProgramming 9 4 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Страница 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...