99
Control Period Write: WT
Section 3-11
3-11 Control Period Write: WT
Function
This command is used to write the control period to a control point.
The Control Period Write (WT) cannot be used at a control point being auto-
tuned.
Cooling
-
side control period can be written to a control point provided that the
E5ZE is a heating and cooling control model.
Setting Data Range
Command
Response
Communications Example
In this example, the E5ZE is operated with Control Period Write (WT) under
the following conditions.
Unit no.:
1
Memory Bank no.: 2
Control Point:
3
Control Period:
5 s
Command
Response
Setting unit
1
Setting time unit
s
Default
0002
Setting data
0001 to 0099
@ W T
s
Setting data
Terminator
FCS
x16
x16
Header code
Control period
*
Unit
x10
x10
x10
x10
Bank
Control
point
00: Control period
01: Cooling-side control period for
heating and cooling models only.
Data code
1
1
0
0
3
2
@ W T
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0
@ 0 1 W T 2 3 0 0 0 0 0 5 4 6
s
*
5 s
Control period
@ 0 1 W T 0 0 4 2
s
Normal end
*