120
Auto-tuning Start: AS
Section 4-1
4-1
Auto
-
tuning Start: AS
Function
This command is used to auto
-
tune a control point.
Auto
-
tuning Start (AS) is not accepted by a control point if the control point is
already being auto
-
tuned or the operation of the control point has been inter-
rupted.
The HB or HS alarm of a control point will not work if the control point is being
auto
-
tuned.
Commands
With Control Point Designated
Auto
-
tuning of All Control Points
If the control point data of the command block is set to A and the data code of
the command block is set to 00, all the control points will be auto
-
tuned simul-
taneously. If the control point data of the command block is set to A and the
data code of the command block is set to 01, all the control points will be auto
-
tuned in sequence.
Sequential Auto
-
tuning of All Control Points:
If the data code of the command block is set to 01, all the control points will be
auto
-
tuned in numerical order.
Response
Communications Example
In this example, control point 3, the unit number of which has been set to 1, is
auto
-
tuned with Auto
-
tuning Start (AS).
Command
@ A S 0 0 0
s
Header code
Terminator
*
Data code
FCS
Control
point
Unit
x16
x16
Always 0
1
0
00: Simultaneous auto-tuning of all control points
01: Sequential auto-tuning of all control points
@ A S 0 A
s
Header code
Terminator
*
Data code
FCS
Unit
x16
x16
Always 0
1
0
@ A S
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0
@ 0 1 A S 0 3 0 0 5 0
s
*