Heater Current Value and SSR Leakage Current Value
Section 5-5
The HB or HS alarm is not valid for the control point that has been desig-
nated.
The operation of the control point that has been designated is stopped.
Response Block with Error Detected
The response block for Heater Current Value and SSR Leakage Current
Value Read (RZ) will include an error code if an error is detected by the E5ZE
while the E5ZE is processing the command.
1.
The response block for Heater Current Value and SSR Leakage Current
Value Read (RZ) does not include read data or an error code if the end
code of the response block is other than 00.
2.
Refer to
2-4 End Codes
and
2-5 Error Codes
.
Communications Example
In this example, the E5ZE is operated with Heater Current Value and SSR
Leakage Current Value Read (RZ) under the following conditions.
Unit no.:
1
Control Point:
3
Heater Current Value: 25.6 A
Command
Response
@ R Z
s
Terminator
*
E
FCS
x16
x16
Unit
Error code
Header code
End code
x16
x16
x10
x10
x10
1
1
1
0
0
0
2
@ 0 1 R Z 0 3 0 0 4 A
s
Heater current
value
*
@ 0 1 R Z 0 0 0 2 5 6 4 8
s
Normal end
25.6 A
*