131
Manual Output Value Write: WO
Section 4-12
Response
4-12 Manual Output Value Write: WO
Function
This command is used to write the percentage of manual output value to a
control point.
1.
Manual Output Value Write (WO) is used with the E5ZE only when the
E5ZE is in manual operation.
2.
The percentage of cooling
–
side output value can be written to a control
point only if the E5ZE is a heating and cooling control model.
3.
The E5ZE operates manually even if the E5ZE detects a sensor input error.
Manual Output Value Write (WO), however, cannot be used with the E5ZE
if the E5ZE detects a sensor input error.
4.
If the E5ZE has an error, the E5ZE cannot operate manually and Manual
Output Value Write (WO) cannot be used with the E5ZE.
Setting Data Range
Command
Response
Communications Example
In this example, the E5ZE is operated with Manual Output Value Write (WO)
under the following conditions.
Unit no.:
1
Control Point:
3
Manual Output Value: 50.0%
@ 0 1 R s 0 0 0 2 0 0 6 2
s
Normal end
200
°
C
*
Setting unit
0.1
Manual output value unit
%
Setting data
0000 to 1000
Always 0
00: Output value
01: The cooling-side output value for heating and
cooling control model only.
@ W O 0
s
Decimal point
Control
point
Terminator
*
Manual output value
FCS
x16
x16
Unit
Setting data
Header code
x10
x10
x10
Data code
x10
1
1
0
0
2
-1
@ W O
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
0
1
0