DeviceNet Explicit Messages Set Values and Measurement
Section 4-4
4-4-7
Set Values for all Control Points
The following variable table is used for setting and monitoring the same set
values for all control points.
Variable Type: 88
• Set the value of X in the addresses as follows:
X: Control point number (0 to 7). Set
“
A
”
all control points. The setting A is
valid for writing only.
•
Set values cannot be changed while auto
-
tuning is being executed.
Note
1.
These parameters can be set only when operation is stopped.
2.
These parameters can be set while auto
-
tuning is being executed.
3.
When external contact inputs are used to set the memory bank, the mem-
ory banks cannot be switched using communications.
4.
The manual output variable can be set only during manual operation. This
applies to both heating and cooling control.
5.
The relationship between the set point and alarm mode is as shown below.
No.
Address
Set value or
measurement value
Default
Data setting or monitoring range
Data type
1
XF00
Memory bank (See note 3.) 0000
Range: 0000 to 0007 (See note 5.)
Numeric
Read/write
2
XF01
Alarm 1 mode (See note
1.)
0000
Range: 0000 to 000C
3
XF02
Alarm 2 mode (See note
1.)
0000
4
XF03
Output operation (direct/
reverse)(See note 1.)
0000
0000:
Reverse operation
0001:
Direct operation
5
XF04
Heating manual output
variable (See note 4.)
0000
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
6
XF05
HB/HS alarm enable set-
ting (See note 1.)
0000
0000:
HB/HS alarm disabled
0001:
HB/HS alarm enabled
Status
Read/write
7
XF06
Heater burnout detection
current value (See note 2.)
0000
Range: 0000 to 01F4 (0.0 to 50.0)
Unit:
0.1 A
Numeric
Read/write
8
XF07
SSR failure detection cur-
rent value (See note 2.)
0000
9
XF08
Cooling manual output vari-
able (See note 4.)
0000
Range: 0000 to 03E8 (0.0 to 100.0)
Unit:
0.1%
Set point
Alarm mode
0000
No alarm
0001
Upper
-
and lower
-
limit alarm
0002
Upper
-
limit alarm
0003
Lower
-
limit alarm
0004
Upper
-
and lower
-
limit range alarm
0005
Upper
-
and lower
-
limit alarm with standby sequence
0006
Upper
-
limit alarm with standby sequence
0007
Lower
-
limit alarm with standby sequence
0008
Absolute
-
value upper
-
limit alarm
0009
Absolute
-
value lower
-
limit alarm
000A
Absolute
-
value upper
-
limit alarm with standby sequence
000B
Absolute
-
value lower
-
limit alarm with standby sequence
000C
HB alarm and HS alarm (general alarm)