Alarm Temperature Write: W%
Section 3-17
3-17 Alarm Temperature Write: W%
Function
This command is used to set the alarm temperatures for alarm 1 or 2 of a con-
trol point.
Setting Data Range
1.
Setting Unit Write (Wt) must be used to set the temperature setting unit of
a control point to 1 or 0.1.
2.
It is unnecessary to set an alarm temperature if HB and HS alarm data is
used as the parameters for Alarm Temperature Write (W%).
Command
When Setting Unit is 1
When Setting Unit is 0.1
Setting unit
1
0.1
°
C or
°
F
°
C
°
F
°
C
°
F
Default
0000
00000
Parameters
Alarm OFF
-999 to 9999
-9999 to 99999
Upper
-
and lower
-
limit alarm
0000 to 9999
00000 to 99999
Upper
-
limit alarm
-999 to 9999
-9999 to 99999
Lower
-
limit alarm
-999 to 9999
-9999 to 99999
Upper
-
and lower
-
limit range alarm
0000 to 9999
00000 to 99999
Upper
-
and lower
-
limit alarm with standby sequence
0000 to 9999
00000 to 99999
Upper
-
limit alarm with standby sequence
-999 to 9999
-9999 to 99999
Lower
-
limit alarm with standby sequence
-999 to 9999
-9999 to 99999
Absolute
-
value upper
-
limit alarm
-999 to 9999
-9999 to 99999
Absolute
-
value lower
-
limit alarm
-999 to 9999
-9999 to 99999
Absolute
-
value upper
-
limit alarm with standby
sequence
-999 to 9999
-9999 to 99999
Absolute
-
value lower
-
limit alarm with standby
sequence
-999 to 9999
-9999 to 99999
HB and HS alarm
---
---
00: Alarm 1
01: Alarm 2
@ W %
s
Decimal point
Control
point
Terminator
*
FCS
x16
x16
Unit
Setting data
Header code
x10
x10
x10
Data code
x10
Bank
Or minus sign (-)
Alarm set value
1
1
0
0
3
2
00: Alarm 1
01: Alarm 2
@ W %
s
Decimal point
Control
point
Terminator
*
FCS
x16
x16
Unit
Setting data
Header code
x10
x10
x10
Data code
x10
Bank
Or minus sign (-)
Alarm set value
x10
1
1
0
0
3
2
-1