Alarm Temperature Read: R%
Section 3-18
Response
Communications Example
In this example, the E5ZE is operated with Alarm Temperature Write (W%)
under the following conditions.
Unit no.:
1
Memory Bank no.:
2
Control Point:
3
Setting Unit:
1
Alarm 1 Temperature: 50
°
C
Command
Response
3-18 Alarm Temperature Read: R%
Function
This command is used to read the alarm temperatures that have been set at a
control point.
Command
Response
When Setting Unit is 1
@ W %
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0
@ 0 1 W % 2 3 0 0 0 0 5 0 3 7
s
Alarm 1
*
50
°
C
@ 0 1 W % 0 0 3 3
s
Normal end
*
00: Alarm 1