128
Ramp Value Read: RR
Section 4-10
Command
Response
Communications Example
In this example, the E5ZE is operated with Ramp Value Write (WR) under the
following conditions.
Unit no.:
1
Memory Bank no.: 2
Control Point:
3
Ramp Value:
10.0 min
Command
Response
4-10 Ramp Value Read: RR
Function
This command is used to read the ramp values that have been set at a control
point.
Command
Setting unit
0.1
Temperature unit
°
C/s
°
F/s
°
C/min
°
F/min
°
C/h
°
F/h
Default
000
Setting data
000 to 999
@ W R 0 0
s
Time
S: Second
M: Minute
H: Hour
Decimal point
Control
point
Data code
Terminator
*
Ramp value
FCS
x16
x16
Unit
Bank
Setting data
Header code
x10
x10
x10
1
1
0
0
-1
@ W R
s
*
FCS
End code
Unit
x16
x16
x16
x16
Header code
Terminator
1
1
0
0
@ 0 1 W R 2 3 0 0 1 0 0 M 3 9
s
*
10.0 min
@ 0 1 W R 0 0 4 4
s
Normal end
*
@ R R 0 0
s
Control
point
Data code
Terminator
*
FCS
x16
x16
Unit
Bank
Header code
1
0