159
Fuzzy Scale 2 Write: Wl
Section 7-5
Response
1.
The response block for Fuzzy Scale 1 Read (Rk) does not include read
data if the end code of the response block is other than 00.
2.
Refer to
2-4 End Codes
.
Communications Example
In this example, the E5ZE is operated with Fuzzy Scale 1 Read (Rk) under the
following conditions.
Unit no.:
1
Memory bank no.: 2
Control point:
3
Fuzzy scale 1:
40.0
°
C
Command
Response
7-5
Fuzzy Scale 2 Write: Wl
Function
This command is used to write fuzzy scale 2 values to a control point for the
E5ZE to determine the speeds of temperature changes due to external distur-
bance.
1.
Fuzzy Scale 2 Write (Wl) cannot be used at a control point being auto
-
tuned.
2.
Fuzzy scale 2 values for a control point being auto
-
tuned will be set auto-
matically when the auto
-
tuning of the control point finishes.
3.
The fuzzy scale 2 value of a control point will be automatically adjusted ac-
cording to the PID constants. The fuzzy scale 2 value can be changed
manually after PID constants are set for the bank.
Setting Data Range
@ R
k
s
Decimal point
Terminator
*
Fuzzy scale 1
FCS
x16
x16
Unit
Read data
Header code
End code
x16
x16
x10
x10
x10
x10
1
1
1
0
0
0
2
-1
@ 0 1 R k 2 3 0 0 7 9
s
*
@ 0 1 R k 0 0 0 4 0 0 7 C
s
Normal end
40.0
°
C
*
Setting unit
0.01
°
C or
°
F
°
C/s
°
F/s
Default
9999
Setting data
0020 to 9999